Module 16: The non-climbable zone

Module 16 of 49 · Part 3 – Barrier essentials: F9/AS1 · About 10 minutes · Sources checked 17 November 2026

A child only needs one good foothold.

Keep the outside of a pool barrier free of footholds: the 1200 mm arc, projections and indentations, horizontal rails, and the 900 mm zone on boundary fences.

Read the module in the flip book below. The cover image is AI-generated and illustrative only. A short quiz is at the end of the module, with answers included.

On-screen flip book · 8 pages

Page 1 of 8

Key learning points

  • Code: a barrier must have no permanent objects or projections on the outside that could help children get over it (F9.3.3).
  • Arc: no ground features or objects outside within 1200 mm of the top of the barrier that would assist climbing (F9/AS1 2.1.6, Figure 2).
  • Projections: anything sticking out (or in) more than 10 mm on the outside face must be at least 900 mm apart vertically (2.1.7).
  • Rails: rails, rods or wires that are not vertical must be at least 900 mm apart vertically (2.1.3).
  • Boundary barriers also need a 900 mm climb-resistant zone on the pool side, starting within 150 mm of the top (2.2.1(d)).

Key terms

TermMeaningWhere
Projection / indentationAnything sticking out from, or recessed into, the outside face of the barrier.F9/AS1 2.1.7
Climbable objectA ground feature or object that would help a child climb.F9/AS1 2.1.6, Fig 2
Non-climbable zoneNZS 8500 term for the area that must be kept clear; F9/AS1 uses the 1200 mm test.NZS 8500 (not reviewed)
900 mm zoneClimb-resistant zone on the pool side of a boundary barrier.F9/AS1 2.2.1(d)

Official references

DocumentVersionUsed for
Building Code clause F9Version as at 15 January 2026; captured 29 Oct 2026F9.3.3
MBIE Acceptable Solutions F9/AS1 & F9/AS2First Edition, effective 27 April 2017; captured 17 Nov 2026AS1 2.1.3, 2.1.6, 2.1.7, 2.2, Figures 1–2
Auckland Council – “Pool area safety checklist”Web page, captured 17 Nov 2026Council inspection guidance